Property Inspection Report
|
||||||||
Final Analysis Home Inspections 5020 Ferrell Pkwy. Virginia Beach VA 23464 |
||||||||
Prepared exclusively for Removed for privacy |
||||||||
xxxx Colchester Cres. Norfolk VA 23504 |
||||||||
|
||||||||
Report ID:
021915 |
||||||||
Inspection Date:
2/19/2015 |
||||||||
Inspected By: Adam Comeau
|
||||||||
757.495.2300 |
||||||||
Date: 2/19/2015 | Time: 09:00 AM | Report ID: cunningham021915 |
Property: xxxx Colchester Cres. Norfolk VA 23504 |
Customer: Removed for privacy |
Real Estate Professional: Virginia Cope Coastal Realty |
Type of Inspection: Home Buyers inspection | Inspection Procedures: American Society of Home Inspectors, Standards of practice | General inspection accessibility: Occupied, furnished, typical access |
Occupancy: Occupied | All Utility services are on?: Yes | In Attendance: Buyer, Buyers Agent |
Type of building: Single Family (2 story) | Square Feet of conditioned space: 1657 | Approximate age of building: 1989 |
# of Bedrooms: 3 Bedrooms | # of Bathrooms: 2 bathrooms | Temperature: 29 |
Weather: Clear, Snow, freezing | Congested with personal property: No | Ground/Soil surface condition: Frozen |
Rain in last 3 days: No | Garage: detached, 1 car | Electric service: 150 amp |
Natural gas service: Yes | Water service (potable): Public (city) | Waste system: public sewage |
Heat system(s): Forced air, Gas Furnace | Cooling system(s): Central AC | The front of the structure faces: East |
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it is satisfactory and appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit does not exists in this home or building.
Information & Disclosures (ID) = Important information you should know about this house or building including, disclosures, alerts, advisories and warnings about typical conditions or circumstances for this home. Not necessarily something abnormal or unusual but critical information that may pose significant concern for health risk, environmental safety or additional cost. These items will be indicated with an Orange Flag
Repair or Replace (RR) = The item, component or unit is not functioning as intended, defective, broken or otherwise needs further inspection and evaluation by a qualified contractor. Items, components or units that should be repaired, replaced or corrected. These will be indicated with a Red Flag
Inspection standards: This inspection was completed in compliance with the professional standards of practice set forth by the American Society of Home inspectors (ASHI)
Purpose and Objective: This inspection is a first look attempt at ascertaining the general condition of a property. It is the purpose of this inspection to discover and disclose those items and concerns that may have an adverse impact on the value of this property and the health and safety of it's occupants. It is important to know that home inspectors are general practitioners with a limited amount of time, abilities and resources designed primarily to focus and report obvious or potential problems. Home inspections are limited to visual observations only. Outside of normal function test, Inspectors do not engage in troubleshooting or diagnostics. The inspection does not include technically exhaustive evaluations, invasive analysis, destructive testing or the use of specialty equipment such as infrared cameras or internal scopes. This inspection and the report only attempts to identify evidence of suspected adverse conditions and make recommendations of further evaluation by specialist or experts in that system.
It is the objective of this inspection and report to provide you the means by which you can progress in an informed manner thereby protecting yourself as much as possible. This may mean obtaining further evaluation and repairs by an expert, purchase price adjustments, escrow of funds for repair, or withdrawing from a buyers purchase agreement altogether. If you are subject to an inspection contingency removal addendum on your purchase contract, your conditions of removing that contingency should be clearly stated with details of expected outcomes. Furthermore, it should also be stated that any dispositions or repairs agreed to should be subject to your re-inspection and final acceptance of satisfactory completion.
Repairs - No matter how big or small, All repairs, corrections or replacements should be requested to be completed by licensed, qualified professionals with copies of their credentials, licensing, labor and product warranties and receipts of work. It is not recommend that you ask the seller to make the repairs unless they are qualified in the trades and you feel confident that they'll do a good quality job. It should be expected and required that all work be accompanied by any required city permits and inspections. Mostly all work except minor repairs require city permits and inspections. Finally, all repairs should be subject to your re-inspection, satisfaction and approval a couple days before closing.
Reinspection - Due to liability restrictions, reinspections are not the policy of Final Analysis home inspections. All repairs or corrections should be completed by qualified, licensed professional in their trade and should be accompanied by permits, work orders, receipts and warranties. If you feel a reinspection is necessary we can provide on a case by case basis and subject to schedule availability. The property inspection contingency removal addendum (PICRA) should be provided to us when the re-inspection is requested. All re-inspections are subject to a minimum fee of $200 and will be accompanied by an updated report.
NOTICE OF URGENCY: If you are buying this property, any discrepancies, concerns or issues revealed in this report should be resolved to your satisfaction before close of escrow and/or taking possession.
Overview: A thorough home inspection was completed at the subject property in accordance with the American Society Home Inspections (ASHI) standards. The inspection reveals that this dwelling has normal wear and tear. Its structure and systems are generally sound, well built and in good repair but with some significant concerns reported. All observations made and items reported here should be carefully reviewed and considered for correction where needed as they are specific to this home and can have a significant impact on it's condition, safety and value.
GENERAL ROOF CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
ROOF SERVICE LIFE REMAINING::
50% - 80% (Good - No concerns outside of normal maintenance) |
ACTIVE / SUSPECTED ROOF / FLASHING LEAKS OBSERVED/DETECTED:
No |
Probability of leakage:
low |
Roof covering material:
Architectural style asphalt shingles |
Viewed roof from:
Ground Binoculars Attic |
Sky Light(s):
None |
Chimney (exterior):
Wood framed metal flue Vinyl siding |
Number of layers:
One |
Roof penetrations or Flashing maintenance or repairs recommended:
No |
Attic Ventilation:
Gable vents Soffit intake vents installed 8x8 static roof outlet vents installed |
1.0 |
ROOF COVERINGS
Comments and observations: Inspected |
Inspection Limitation - The roof inspection was limited to visible areas of the shingle covering due to
snow and ice covering at the time of the inspection (Item 1). It was noted that a large portion of the roof
covering was visible and inspected.
1.0 (Item 1)
|
1.1 |
FLASHINGS
Comments and observations: Inspected |
Maintenance / Repair - The metal flashing cap at the top of framed wood chimney is rusting and
deteriorating (Item 1). recommend preventative maintenance and repairs before it fails and leaks.
1.1 (Item 1)
|
1.2 |
SKYLIGHTS, CHIMNEYS and Other ROOF PENETRATIONS
Comments and observations: Inspected |
1.3 |
ROOF DRAINAGE SYSTEMS
Comments and observations: Not Present |
1.4 |
ATTIC VENTILATION
Comments and observations: Inspected |
(1) Deficiency- Vent channels are missing from above the insulation in the rafter bays of the vaulted ceilings
(Items 1 and 2). Vent channels allow the soffit intake air to travel up to the roof outlet vents to the outside
atmosphere (Item 3). Otherwise the heated air becomes trapped in the knee-wall areas thus defeating the
needed ventilation in this area. Vent channels have been used in most construction for 25-30 years but it is
not uncommon for older homes to not have these.
1.4 (Item 1)
1.4 (Item 2)
1.4 (Item 3)
|
|
(2) Defect - The right side gable vent (when facing the front of the house) is physically damaged, lifted and is
subject to harmful vermin intrusion (Item 4). Recommend professional repairs be completed by a qualified
contractor.
1.4 (Item 4)
|
|
(3) General Statement - Attic ventilation plays an important role in reducing the heat loads in your attic,
dissipating trapped moisture and contributing to the overall health of your attic/roof system. A poorly
ventilated attic can reduce HVAC performance, shorten shingle life, and will promote rot of wood materials
if moisture can't escape. Poor eave/soffit vents are the # reason for poor attic ventilation. Typically newer
homes are better ventilated but older homes 20+ years, should be reviewed for improvement. It is important
to remember that you need balanced intake vents along with outlet vents for good air flow. Installing just a
power fan may not accomplish this. See more ventilation tips here
Attic is ventilated |
GENERAL EXTERIOR CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
Siding material:
Vinyl |
Trim materials:
Wood |
Exterior Entry Doors:
Steel |
Appurtenance:
Deck with steps Covered porch |
Driveway:
Concrete |
Evidence of water intrusion at exterior walls windows doors:
No |
2.0 |
WALL CLADDING FLASHING AND TRIM
Comments and observations: Inspected |
2.1 |
DOORS (Exterior)
Comments and observations: Inspected |
Deficiency - The rear patio door weather stripping is poorly installed and not sealing to the door as
designed and may permit water intrusion and unconditioned air infiltration (Item 1). Recommend
professional repairs be completed by a qualified contractor.
2.1 (Item 1)
|
2.2 |
WINDOWS
Comments and observations: Inspected |
Observation - The vinyl replacement windows are dated 2008 (Item 1).
2.2 (Item 1)
|
2.3 |
DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS
Comments and observations: Inspected |
Defect, Safety - The garage steps handrails are loose, detached and are a trip and fall hazard (Item 1).
Recommend professional repairs be completed by a qualified contractor.
2.3 (Item 1)
|
2.4 |
VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PARKING LOTS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)
Comments and observations: Inspected |
(1) Deficiency - Crawlspace vents are below exterior mulch grade and are allowing harmful water intrusion
into the crawlspace (Item 1). Recommend professional repairs be completed by a qualified contractor.
2.4 (Item 1)
|
|
(2) General Information - Positive grading and drainage are essential to the welfare of a property, and are usually the primary concern of architects and builders. Moisture can deteriorate most surfaces, cause soil movement and erosion, and undermine the structures foundation. The ideal site will be graded to conduct water away from a building. In fact, the ideal building will be surrounded by hard surfaces that slope way from the exterior walls, the interior floors will be several inches higher than the exterior grade, and the building will have gutters and downspouts and a system of drainage designed to prevent any moisture from threatening the foundation or the living space. Unfortunately, many properties do not meet this ideal, conditions on most can generally be improved, and all need to be monitored and maintained to prevent damage. Also, inspectors cannot see inside area drains and do not water-test them, but they can become blocked by debris, occluded by silt, and damaged by movement. Therefore, buyers should question sellers about the functionality of any such system, have it serviced by a specialist, or assume the risk of having a system that does not function well and the damage that might result |
2.5 |
EAVES, SOFFITS AND FASCIAS
Comments and observations: Inspected |
2.6 |
Garage, Garage door, opener safety reverse (if applicable)
Comments and observations: Inspected |
(1) Safety - The garage door return spring safety cable is not installed and could cause injury (Item 1). The
safety cable helps contain flying parts in the event of breakage (Item 2).
2.6 (Item 1)
2.6 (Item 2)
|
|
(2) Inspection Limitation - Some areas of the garage were congested with personal property at the time of
the inspection (Item 3). The garage inspection was limited to visible areas only.
2.6 (Item 3)
|
|
(3) Workmanship Defect - The garage door not properly flashed with drip cap flashing at header trim (Item 4).
Drip cap flashing provides water shed away from the door opening at the top (Item 5). Caulk is not
acceptable. In fact caulk can trap water in. The affected areas are subject to water intrusion and damage
to the wall structure. Correction is recommended as a preventative measure. At a minimum these areas
should be monitored for water stains and wetness before any serious damage occurs.
2.6 (Item 4)
2.6 (Item 5)
|
This inspection does not test for or report on the presence of MOLD or other indoor air quality issues or hazards.
GENERAL INTERIOR CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
Ceiling Materials:
Drywall, Sheet rock, Gypsum Plaster veneer |
Wall Material:
Drywall, Sheetrock, Gypsum Plaster knock-down |
Floor Covering(s):
Carpet Hardwood T&G Tile |
Window Types:
Vinyl Tilt feature Double-hung Thermal/Insulated |
Interior Doors:
Hollow core Masonite Raised panel |
Cabinetry:
Wood |
Countertop:
Laminate |
3.0 |
CEILINGS
Comments and observations: Inspected |
3.1 |
WALLS
Comments and observations: Inspected |
Observation, Mold - Observed evidence of fungi growth on the wall behind the baseboard to the right side
of the rear patio door (Items 1 and 2) and behind the washer and dryer in the garage (Item 3). This is just
an observation disclosure. It is beyond the scope and qualifications of a home inspection to inspect, test
or determine if this growth is or is not a health hazard. All homes have some form of mold, fungi and
sporing. Most molds are not harmful but extreme amounts can cause allergenic complications.Some
molds are toxic and poisonous but the documented cases are rare. The underlying cause is moisture.
The source of moisture must be cured, any un-cleanable materials discarded and other areas cleaned and
dried. If the affected area is greater than 30 square feet you may consider hiring a mold remediation
specialist who can provide expert testing, evaluation and correction along with associated cost.
3.1 (Item 1)
3.1 (Item 2)
3.1 (Item 3)
|
3.2 |
FLOORS
Comments and observations: Inspected |
Deficiency - Potential vermin entry point observed in the water heater closet at the floor (Item 1).
Recommend professional repairs be completed by a qualified contractor.
3.2 (Item 1)
|
3.3 |
STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Comments and observations: Inspected |
Safety - Pickets at railings are spaced greater than 4" apart (Items 1 and 2). This is safety hazard for
small children and no longer permitted in new construction. Recommend using precautions with small
children such as safety barrier or netting.
3.3 (Item 1)
3.3 (Item 2)
|
3.4 |
COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS
Comments and observations: Inspected |
Deficiency - The kitchen laminate counter tops are deteriorating in several locations, delaminating and in need of general repair. Recommend professional cost estimates repairs be completed by a qualified counter top contractor as needed. |
3.5 |
DOORS (REPRESENTATIVE NUMBER)
Comments and observations: Inspected |
Deficiency - The garage door has no weather seal (Item 1). This is typical for older homes but not
permitted when doors are replaced or in modern construction. Poorly sealed garage doors can allow
seepage of dangerous fumes, allow unconditioned air infiltration and decrease thermal efficiency of the
home. Recommend professional repairs be completed by a qualified contractor.
3.5 (Item 1)
|
3.6 |
WINDOWS (REPRESENTATIVE NUMBER)
Comments and observations: Inspected |
Defect - The front bedroom window top sash is physically damaged and has cracked glass (Item 1).
Recommend professional replacement be completed by a qualified window contractor.
3.6 (Item 1)
|
GENERAL STRUCTURAL CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
Is there significant structural faiulre/damage/distress was observed/suspected:
NO |
Crawl space access point:
Exterior |
Method used to observe Crawlspace:
Crawled |
Was there evidence of Termits- Powder post beetles or wood destroying fungus- mold- mildew- spores:
YES Inactive Crawlspace framing Termites |
Was there evidence of Harmful Moisture / Water Conditions at foundation/crawlspace:
Standing water YES |
Crawlspace ventilation:
Adequate |
Attic access:
Ceiling scuttle hole Knee-wall |
Method used to observe attic:
Crawled |
Was there evidence of Harmful Moisture Conditions in Attic:
No |
Foundation type:
Crawlspace |
Floor Structure:
Conventional wood framed |
Wall Structure:
Conventional wood frame |
Columns or Piers:
Masonry block |
Ceiling Structure:
Conventional wood frame |
Roof Structure:
Engineered wood trusses |
Roof-Type:
Gable |
4.0 |
FOUNDATIONS, SLABS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. Fungus or wood destroying insects)
Comments and observations: Inspected |
(1) Observation - There is evidence of vermin or rodent nesting/infestation in the crawlspace. Observed feces, nesting materials and insulation tunneling. It is not unusual to see some level of vermin in these spaces of many homes. Vermin can do significant damage to wiring, insulation and building materials and can block critical ductwork such as dryer, stove and bathroom vents. Typical suspects are rodents, birds and squirrels. Feces and carcasses can present a health hazard. It is recommended that you have all holes and entry points blocked or sealed. Pest control operators and exterminators are the professionals that do this kind of work. | |
(2) Defect - The Pier footing excavations at the throughout the crawlspace foundation were not back-filled
after construction (Items 1-3). These excavations have collected water and promoted erosion, have
undermined the footings and lead to some minor settlement. Typical remedy is to fill and pack low areas
with sand so it is level with existing crawlspace grade. Cost to cure can be expensive. Recommend
further evaluation and cost estimates be obtained from a qualified building contractor.
4.0 (Item 1)
4.0 (Item 2)
4.0 (Item 3)
|
4.1 |
VAPOR RETARDERS (Crawl pace)
Comments and observations: Inspected |
Defect - The vapor barrier (plastic) on the crawlspace ground is missing or pulled away in multiple areas
and is below water level in some areas and getting flooded, allowing water to stand or pool on surface. A
vapor barrier provides added protection to the floor system and building components from harmful moisture,
dampness and evaporation that can enter from ground. vapor barrier should be at least 6mil and provide
100% coverage. It should be trimmed and fit around columns, overlapped at seams and pinned down to
prevent movement or separation. A qualified person should repair or replace as needed.
4.1 (Item 1)
|
4.2 |
STRUCTURAL FRAMING walls, floors, ceilings (where visible)
Comments and observations: Inspected |
(1) Defect - Improper substandard repairs. Observed approximately 4 improperly "scabbed" floor joists
beneath the foyer that are subject to strain, fastener sheer and separation (Items 1 and 2). The typical
repair is to "full length sister the damaged floor joists from girder beam to sill plate. Recommend further
evaluation, cost estimates and repairs be completed by a qualified building contractor.
4.2 (Item 1)
4.2 (Item 2)
|
|
(2) Defect - Water intrusion observed beneath the front door way. Moisture content in the wood is 46%
(Saturated) and is subject to wood destroying organisms and rot damage (Items 3-4). Repairs should
include remedy of the moisture intrusion source. Recommend further evaluation and professional repairs be
completed by a qualified contractor.
4.2 (Item 3)
4.2 (Item 4)
|
|
(3) Defect - Top plate termite damage (Item 5) and 1 termite damaged and improperly scabbed with a 2x4,
rafter (Item 6) observed in the attic knee-wall above the patio door/kitchen area. Both affected areas will
require repairs and should be completed by a qualified building contractor.
4.2 (Item 5)
4.2 (Item 6)
|
|
(4) Observation - Substantial prior termite damage (Items 7-10) and repairs have been completed throughout
the entire crawlspace, including new girder beams and sistered floor joists in the majority of all areas.
4.2 (Item 7)
4.2 (Item 8)
4.2 (Item 9)
4.2 (Item 10)
|
4.3 |
STRUCTURAL MASONRY, COLUMNS, PIERS, CONCRETE SLAB
Comments and observations: Inspected |
Defect - Observed multiple dry stacked, sinking and leaning masonry piers. Dry stacked piers are subject
to separation and should be stacked and secured with approved mortar between the blocks. The piers are
also sinking into the soft, saturated sand fill and have begun to lean and separate from the girder beams
and over time can lean to structural settlement and floor sag. Recommend further evaluation and
professional repairs be completed by a qualified contractor.
4.3 (Item 1)
4.3 (Item 2)
|
4.4 |
ROOF STRUCTURE AND ATTIC
Comments and observations: Inspected |
Observation - There is evidence of vermin or rodent nesting/infestation in the attic. Observed feces (Item
1), nesting materials, insulation tunneling (Item 2), and dead vermin (Item 3). It is not unusual to see some
level of vermin in these spaces of many homes. Vermin can do significant damage to wiring, insulation and
building materials and can block critical ductwork such as dryer, stove and bathroom vents. Typical
suspects are rodents, birds and squirrels. Feces and carcasses can present a health hazard. It is
recommended that you have all holes and entry points blocked or sealed. Pest control operators and
exterminators are the professionals that do this kind of work.
4.4 (Item 1)
4.4 (Item 2)
4.4 (Item 3)
|
4.5 |
CRAWL SPACE VENTILATION (if applicable)
Comments and observations: Inspected |
Disclosure: Buried, concealed or otherwise hidden piping including supply pipes and drain pipes that are not visible, are specifically excluded from this inspection. Questionable and suspect piping systems should be have an invasive, exhaustive evaluation completed by a plumbing contractor who may use video cameras, pressure testing and other means to determine the quality of pipes that are not possible during a visual home inspection.
GENERAL PLUMBING SYSTEM CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
Probability of plumbing leaks:
Low |
Active leaks observed:
No |
Domestic Potable Water Source (not yard irrigation):
Public (municiple) |
Plumbing waste system:
City sewage |
Water Supply pipe (from street meter):
Polybutylene (PB) (inferior materials) |
Water Distribution pipes (inside structure - visible areas only):
Polybutylene (PB) (inferior materials) |
Plumbing Waste / Drain pipe materials:
Copper |
Domestic hot water source:
Electric storage tank |
Water Heater Capacity:
47 Gallon (2 people) |
Water heater service life remaining:
20% or less (plan for replacement, consider cost) |
Hot water temperature:
110-120 deg F. (low) |
5.0 |
PLUMBING DRAIN, WASTE AND VENT SYSTEMS
Comments and observations: Inspected |
5.1 |
PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Comments and observations: Inspected |
(1) Polybutylene plastic plumbing supply lines (PB) are installed in the subject house (Items 1 and 2).
Polybutylene (AKA Quest pipes) millions of homes where plumbed with PB in the 80's and 90's but
installations ceased in the middle 90's when it was realized to be an inferior piping due to it's higher
than normal failure rate. Plastic insert fittings were used in the early years which had a very high failure
rate. Copper and Brass insert fittings used in later years have dramatically reduced the failure rate but
by then it was too late and was abolished from use altogether. This subject house has copper
fittings (Items 3 and 4). Many homes have been completely re-plumbed by now, especially the ones
with plastic fittings. Re-plumb can be very expensive. Most homes are re-plumbed using PEX or CPVC
pipes but some use copper. For further details contact the Consumer Plumbing Recovery center at 1-800-392-7591 or the web at http://www.pbpipe.com Please note that much of the information on the
web about PB is "for profit" so take it with a grain of salt.
5.1 (Item 1)
5.1 (Item 2)
5.1 (Item 3)
5.1 (Item 4)
|
|
(2) FYI Disclosure - Polybutylene (PB) plastic plumbing "yard service pipe from meter is installed at this
house (Item 5). Polybutylene has been used in this area for many years, but has had a higher than normal
failure rate, and is no longer being widely used. The blue PB used for yard service has a fairly good
performance record relative the the grey PB used inside some homes. Any use of PB is disclosed for your
information. For further details contact the Consumer Plumbing Recovery center at 1-800-392-7591 or the
web at http://www.pbpipe.com
5.1 (Item 5)
|
|
(3) Deficiency - The water heater cold water shut off gate valve has previously leaked and has sealed its self
with a corrosion plug (Item 6). Recommend professional replacement of the valve with a higher quality ball
valve be completed by a qualified plumbing contractor.
5.1 (Item 6)
|
|
(4) Defect - Observed loose hanging, unsecured piping in the crawlspace beneath the kitchen area (Item 7).
Pipes that are not secured can become loose or leak at fittings from pipe hammer, whip or strain.
Recommend that all piping be secured as required using approved methods and materials and completed
by a qualified contractor.
5.1 (Item 7)
|
5.2 |
HOT WATER SYSTEMS
Comments and observations: Inspected |
(1) Safety - The T&P (Test and Pressure) valve on water heater is not properly plumbed with a copper
discharge pipe which should extended to within 3" of floor surface or vented to the outside which is
required for safety (Item 1). Discharge pipe must be of copper, steel or CPVC material. PVC is not
allowed. Recommend professional repairs be completed by a qualified plumbing contractor.
5.2 (Item 1)
|
|
(2) Aging water heater - The water heater has reached or exceeded it's manufactured service life (Mfg. 2005) and is due for replacement. Statistically it is likely to fail which could leave you without hot water or worse, cause flooding and water damage. Water heaters should be replaced by a licensed plumbing contractor who should procure any required municipal permits and inspections as required by the city. If work is completed before a real estate closing/settlement it should be written subject to your satisfaction, reinspection and acceptance before closing. | |
(3) Defect - The replaced/updated water heater located in an interior space does not contain a drip pan and
drain pipe (Items 2 and 3). In the event of a leak, significant property damage can be the result. Some low
elevation installations may require a drain reservoir and pump. These requirements does not apply to water
heaters located in garages or attached sheds or other areas where there's no risk of water damage.
Updated or replaced water heaters must meet this requirement. It is recommended that this condition be
professionally corrected by a qualified plumbing contractor or other qualified person using approved
materials and in compliance with current building codes.
5.2 (Item 2)
5.2 (Item 3)
|
|
(4) General safety information about hot water temperatures - Hot water systems can be a scald
hazard and a source of disease. Water temperatures higher than 130 deg F. can be a scald hazard.
Water temperatures less than 120 deg. F. is considered ideal for the growth of harmful bacteria inside
the tank–such as Legionella (Item 4). Monitor your hot water temperatures for safety.
Information sources: http://EPA/Legionella: Drinking Water Health Advisory 5.2 (Item 4)
|
5.3 |
MAIN WATER SHUT-OFF DEVICE (Describe location)
Comments and observations: Inspected |
FYI - Primary water shut off is at municipal water meter. |
5.4 |
FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks)
Comments and observations: Inspected |
Defect, Safety - Active nat. gas leak observed at the nat. gas pipe fitting in front of the A/C evaporator coil
in the lower attic (Items 1 and 2). Recommend further evaluation and professional repairs be completed by
a qualified HVAC contractor.
5.4 (Item 1)
5.4 (Item 2)
|
5.5 |
MAIN FUEL SHUT OFF (Describe Location)
Comments and observations: Inspected |
FYI - The main fuel shut off is at the gas meter. |
GENERAL ELECTRICAL CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
Electrical inspection limitations:
None, Inspected in accordance with ASHI standards of practice. |
Electrical Service Cable (from utility pole or transformer):
Below ground Aluminum 2/0 cable |
Location of MAIN electric service panel(s):
garage |
Electric service and panel(s):
150 AMP Adequate capacity Main breaker Circuit breakers |
Branch circuit wiring/distribution for 15 and 20 AMP lighting and outlets:
Solid Copper Romex - NM plastic (normal - typical) Grounded (3 prong outlets) |
Do smoke detectors respond to test?:
Yes |
6.0 |
SERVICE ENTRANCE CONDUCTORS
Comments and observations: Inspected |
6.1 |
SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
Comments and observations: Inspected |
Defect, safety - The A/C condenser disconnect is heavily weathered and rusted, is detached and
separated, high voltage wires are exposed, is subject to water intrusion and is a shock and electrocution
hazard (Item 1). Recommend professional repairs be completed by a qualified electrical contractor.
6.1 (Item 1)
|
6.2 |
BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
Comments and observations: Inspected |
Defect - Observed 2 breakers that continuously trip when reset in the service panel on the lower right hand
side of the service panel (Items 1 and 2). The reason for the breakers continuously tripping is unknown and
may be caused by a direct short somewhere on the circuits. Recommend further evaluation and
professional repairs be completed by a qualified electrical contractor.
6.2 (Item 1)
6.2 (Item 2)
|
6.3 |
CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
Comments and observations: Inspected |
(1) SAFETY - There are one or more covers missing from electrical outlets in multiple locations (Items 1 and
2). Covers reduce the risk of fire and shock. Install all outlet and switch covers where needed.
6.3 (Item 1)
6.3 (Item 2)
|
|
(2) Safety - Water heater high voltage junction box is loose and hanging in the wall, is subject to detachment
and is a shock and electrocution hazard (Item 3). Recommend professional repairs be completed by a
qualified electrical contractor.
6.3 (Item 3)
|
|
(3) Defect - Vermin damaged wire insulation observed in the upper attic near the ceiling scuttle hole that is a
shock and electrocution hazard (Item 4). Recommend professional repairs be completed by a qualified
electrical contractor.
6.3 (Item 4)
|
|
(4) Defect, Safety - The upstairs loft floor outlet is detached and separated, wires are exposed and is a shock
and electrocution hazard (Item 5). Recommend professional repairs be completed by a qualified electrical
contractor.
6.3 (Item 5)
|
|
(5) Defect - The A/C condenser high voltage wire conduit is not secured to the exterior wall, is loose and
hanging from the disconnect, is subject to detachment and water intrusion and is a shock and
electrocution hazard (Item 6). Recommend professional repairs be completed by a qualified electrical
contractor.
6.3 (Item 6)
|
6.4 |
POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE
Comments and observations: Inspected |
6.5 |
OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Comments and observations: Inspected |
Safety - The left side of the kitchen sink outlet (Item 1) and the dining room bar sink outlet (Item 2) are not
GFCI protected and is a shock and electrocution hazard. All wet area outlets are required to be GFCI
protected for safety. Recommend professional repairs be completed by a qualified electrical contractor.
GFCI's save lives.
6.5 (Item 1)
6.5 (Item 2)
|
6.6 |
OPERATION OF AFCI (ARCH FAULT CIRCUIT INTERRUPTERS)
Comments and observations: Inspected |
Information/Disclosure - Non Arch Fault Circuit Interrupts , SAFETY - This home was built before
AFCI technology and therefore is missing some or all AFCI protection in bedrooms. AFCI's protect
against shorts, sparking and fires.. Recommend consider upgrading to AFCI protection.
“Older homes are statistically more vulnerable to electrical fires. Extra protection for older homes is provided by the gradual replacement, over time, of non-AFCI-protected receptacles with new AFCI-protected ones.” The NEC AFCI's prevent fires. Click here for more information on AFCI's |
6.7 |
SMOKE DETECTORS
Comments and observations: Inspected |
6.8 |
CARBON MONOXIDE DETECTORS
Comments and observations: Inspected |
Safety - There is no carbon monoxide detector found in this home with nat. gas appliances, a wood burning fireplace and an attached garage. It is recommended that one be installed according to the manufacturer's instructions. Read more about CO2 poisoning and safety at Consumer Products Safety Commission. |
GENERAL HEAT SYSTEM CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
HEAT SYSTEM - SERVICE LIFE REMAINING::
30% - 50% (Fair - No immediate cost concerns ouside of maintenance/repairs) |
Heat Type:
Natural Gas, Forced air furnace |
Heat system(s) performance:
Satisfactory |
Heat system(s) capacity:
Satisfactory |
Heat System Energy Source:
Natural gas |
Number of Central Heat Systems:
One |
GENERAL AC/ HP SYSTEM CONDITION / RATING:
Not rated |
HEAT PUMP / AC - SERVICE LIFE REMAINING::
20% or less (plan for replacement, consider cost) |
Cooling Equipment Type:
Traditional central AC, split system |
AC/Heat Pump system(s) performance:
Not tested, exterior temp to low. |
AC/Heat Pump system(s) capacity:
Satisfactory |
Number of Central AC / HP systems:
One |
Number of conditioned zones in the house/building:
2 |
Ductwork:
insulated flex duct |
Filter Type:
Disposable |
Types of Fireplaces:
Factory pre-fab metal Wood burning |
Number of operable fireplaces:
One |
Number of Woodstoves:
None |
7.0 |
HEATING, FURNACE EQUIPMENT
Comments and observations: Inspected |
Heat Equipment Performance - The temperature rise test was performed by taking temperature readings
of the heat supply and return air to determine if it is within factory specifications. This furnace specifies a
temperature rise of 25 - 55 degrees F. The actual temperature rise reading is 32 degrees F (Items 1 and 2).
This indicates satisfactory performance and the system is functioning as designed.
7.0 (Item 1)
7.0 (Item 2)
|
7.1 |
PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM
Comments and observations: Inspected |
7.2 |
AC COOLING, HEAT PUMP AND AIR HANDLER EQUIPMENT
Comments and observations: Inspected |
(1) Aging AC equipment - The A/C system is aging and has reached its service life expectancy. Replacement in the near future is inevitable and should be planned and budgeted for. At a minimum you may consider having it cleaned, served and tested by a qualified HVAC contractor in addition to further protection by obtaining a whole house warranty during purchase. | |
(2) Deficiency - It was noted that the outdoor condenser has been replaced (Mfg. 2006) but matched up with an older indoor evaporator coil (Mfg.1989). This may have created what's called a mis-match. Some AC and Heat Pump coils can be matched if the same manufacture is used. But with SEER ratings and modern changes to these systems it is normally not recommended to change one without the other. This is a poor quality practice that was never acceptable and is currently illegal to do. Mis-matching system coils can degrade efficiency, and limit life expectancy. Recommend further evaluation and professional repairs be completed by a qualified HVAC contractor. | |
(3) Disclosure - Older design - This A/C system is designed for use with R22 refrigerant AKA "Freon®"
which is now considered obsolete. R22 has been replaced with R410a refrigerant; AKA "Puron®". As a
homeowner or home buyer considering a purchase, it’s important that you understand the difference so
you can make the best decision for your system while considering your purchase.
R-22 - Often referred to by a brand name like Freon® - As of 2010, R-22 was outlawed for use in new air conditioning systems - R-22 is a hydro-chlorofluorocarbon (HCFC) which contributes to ozone depletion - Is very expensive (cost prohibitive) and will increase as limited supplies are depleted. - R424A is an R22 alternative that can be used in older R22 systems that is ozone friendly but it is almost as expensive as R22 and not as efficient. R-410A - Often referred to by a brand name like Puron®. - Has been approved for use in new residential air conditioners. - Is a hydro-fluorocarbon (HFC) which does not contribute to ozone depletion. - Will become the new required standard for U.S. residential air conditioning systems in 2015 - Can not be used in R22 designed systems. - Is low in price. - R-410A offers greater efficiency, saving you in energy costs, and is much better for the environment. What this means - - We can not determine if the system actually uses R22 or the low efficiency substitute R424A which may reduce system performance. - R22 systems are typically cost prohibitive to repair because of the high cost of R22 or R424A. - Older R22 refrigerant line-set (copper suction and liquid pipes) may require replacement when changing to R410a. - You may be forced to replace the R22 system in 2015. The typical course of action is to replace the A/C system with a modern R410 system. |
|
(4) Deficiency - The insulation sleeve on suction line is missing at the condenser unit (Item 1) and the air
handler (Item 2). Missing insulation on suction line can cause energy loss and condensation. Recommend
maintenance repair as needed.
7.2 (Item 1)
7.2 (Item 2)
|
|
(5) Defect - Improper AC condensate drain and or trap configuration. The drain should contain a trap with a
vent after the trap (Items 3 and 4). Improper configuration will reduce efficiency and performance of the
system and can lead to clogged drain, back-ups and water damage. Recommend proper repairs be
completed by a qualified HVAC contractor using approved methods and materials. Urgency for repair is at
your discretion.
Note: Traps are designed to prevent external air from entering the AC system. Vents are designed to prevent a vacuum which can trap water in the pipe and lead to overflow. Vents should always be installed were the water leaves the trap. 7.2 (Item 3)
7.2 (Item 4)
|
|
(6) Defect - Refrigerant line is poorly sealed and missing the protective rubber grommet at the plenum and is
subject to rubbing on the knife edge of the cabinet causing refrigerant leaks (Item 5). Have properly and
professionally corrected as needed to ensure an air tight seal and to prevent chaffing on the cabinet knife
edge.
7.2 (Item 5)
|
|
(7) Condensate drain failure - The condensate drain is not functioning as designed. Observed condensate
water in overflow pan (evidence of rust or currently contains water) (Item 6). Note: failed condensate drains
in attic locations or other interior spaces can cause significant water damage to ceilings and walls. Have
further evaluated and repaired as needed by a qualified HVAC contractor.
7.2 (Item 6)
|
|
(8) Inspection restriction - The A/C system was NOT run tested for cooling performance because the outside air temperature is 65 degrees or less which would not provide accurate readings and could also risk damage to the equipment. The A/C system inspection was visual only. Given these circumstances, It is recommended that you have the cooling performance test be completed by a qualified HVAC contractor. If this is a home purchase, this should be done before close of escrow and taking possession of the property. |
7.3 |
PRESENCE OF INSTALLED AC/HP SOURCE AIR IN EACH ROOM
Comments and observations: Inspected |
7.4 |
NORMAL OPERATING CONTROLS
Comments and observations: Inspected |
7.5 |
DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments and observations: Inspected |
(1) Dirty HVAC ducts - The ductwork appears to need professional cleaning. Visible areas of the duct/air
movement system show dust and dirt buildup which can degrade system performance and indoor air
quality (Items 1 and 2). Dirty ducts can contain allergens which can diminish indoor air quality and cause
problems for individuals with allergies. Some duct materials such as duct board can not be cleaned and
may require replacement. It is recommended that you seek further evaluation and remedy from a licensed
and NADCA certified duct cleaning and repair contractor.
7.5 (Item 1)
7.5 (Item 2)
|
|
(2) Doors not undercut - Interior passage doors are not sufficiently undercut to allow HVAC return airflow
when the doors are closed (Items 3 and 4). With a forced air system that has a central return, the doors
must have a gap between the door and floor that will allow return air flow and circulation when the doors are
closed. Otherwise the room will become pressurized and not cool or heat sufficiently. 1" gap is adequate
and most doors are designed to be trimmed off the bottom for this purpose.
7.5 (Item 3)
7.5 (Item 4)
|
|
(3) Information - This homes HVAC system contains manual zone dampers at the supply plenum (Items 5
and 6). You can't see if the dampers are open or closed but you can tell by the position of the lever (Item
7). When the lever is parallel (in the same direction) as the duct, it is open, when the lever is perpendicular
(opposite direction of the duct) it is closed. 45 degrees would be half open. Zone dampers are simply air
valves inside the ductwork that allow you to control the air flow and comfort levels to different zones in the
home. For example, you may want to push more AC to the upstairs zone during the summer season. In
that case you would partially or fully close the damper that feeds the downstairs ductwork and fully open
the upstairs damper. In the summer time it would be the opposite. Remember no matter what season it is,
heat rises and cold air falls.
7.5 (Item 5)
7.5 (Item 6)
7.5 (Item 7)
|
|
(4) Maintenance - The disposable return filter is clogged and is dirty (Item 8). The filter needs to be replaced.
Note: a restricted return air filter can cause reduced air flow, reduced efficiency and damage to equipment.
7.5 (Item 8)
|
|
(5) Defect - Observed a physically damaged, crushed and improperly repaired (Taped) duct beneath the
kitchen area (Item 9). Recommend professional repairs be completed by a qualified HVAC contractor.
7.5 (Item 9)
|
7.6 |
CHIMNEYS, FLUES AND VENTS (for fireplaces, water heaters or heat systems)
Comments and observations: Inspected |
SAFETY - Inadequate flue pipe support - Metal flue pipe at Furnace is not properly supported (Item 1). Flue
pipes must be sufficiently supported with straps, brackets or otherwise secured using approved methods
that will prohibit the pipe from moving, separating or detaching at connections which can permit harmful,
hot, poisonous exhaust gases into the structure. A common cause of this is where the flue pipes pass
through the roof and are affected by wind loads above the roofline which can cause stress and movement
on the pipes. Have this problem further evaluated and corrected as needed by a licensed,
qualified professional. The completed work should be subject to your re-inspection, satisfaction
and acceptance.
7.6 (Item 1)
|
7.7 |
SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove)
Comments and observations: Inspected |
7.8 |
GAS/LP FIRELOGS AND FIREPLACES
Comments and observations: Inspected |
GENERAL INSULATION CONDITION / RATING:
Poor (Not functioning as designed, worn out, safety concerns, additional expense.) |
Attic insulation:
neglegible Improvements recommended Loose or blown in fiberglass Approx. R-11 poor |
Wall insulation:
concealed, not visible, not inspected |
Floor System Insulation:
Batts Fiberglass R-13 Good Typical for age |
Bathroom steam vents:
Fan Window |
Dryer Power Source:
220 Electric NOTE: This dryer outlet requires a 3 prong plug |
Dryer duct (built in):
Metal |
8.0 |
INSULATION IN ATTIC / CEILING
Comments and observations: Inspected |
Defect - Attic insulation has vermin/rodent damage and is negligible below R-11 (Items 1-4) and
no longer meets the insulation certificate standard of R-30 (12 Inches) (Item 5). The thickness has been
tramped down and is no longer effective or functioning as designed.It is deficient and will need
correction. It does not meet the current standards or R factor of 38 which is recommended by the
Department of Energy. The attic or ceilings is where you'll loose (or gain) the most amount of heat
transfer. Consideration should be given to upgrading. It is cost effective and will increase the thermal
efficiency of your home.
Visit these links and learn more about your homes insulation: See US Dept of Energy insulation consumer guide | See Insulation fact Sheet. | See Insulation calculator and estimators | Dept of Energy insulation zone map 8.0 (Item 1)
8.0 (Item 2)
8.0 (Item 3)
8.0 (Item 4)
8.0 (Item 5)
|
8.1 |
Wall insulation (if visible)
Comments and observations: Inspected |
(1) Deficiency - Wall Insulation is missing in outer wall above fireplace where it was not insulated inside the
chimney chase (Item 1). Recommend insulating as needed.
8.1 (Item 1)
|
|
(2) Defect - Wall insulation is missing in the lower attic interior wall to the left of the attic door (Item 1) and in
the upper attic above the living room window (Item 2). Recommend professional repairs be completed by a
qualified contractor.
8.1 (Item 2)
8.1 (Item 3)
|
|
(3) Deficiency - Observed areas in the dining room wall above the patio door (Item 4) and the wall above the
refrigerator (Item 4) that have missing insulation as evidenced by thermal imaging. Recommend
professional repairs be completed by a qualified insulation contractor as needed.
8.1 (Item 4)
8.1 (Item 5)
|
8.2 |
INSULATION UNDER FLOOR SYSTEM
Comments and observations: Inspected |
Defect - Floor insulation batts are loose or fallen in multiple locations of the crawlspace (Items 1-3). Repair
or replace as needed.
8.2 (Item 1)
8.2 (Item 2)
8.2 (Item 3)
|
8.3 |
VENTING SYSTEMS (Kitchens, baths and laundry)
Comments and observations: Inspected |
(1) Deficiency - The dryer vent connector is detached and separated in the garage . Recommend professional
repairs be completed by a qualified contractor.
8.3 (Item 1)
|
|
(2) Defect, Safety - Dryer duct is venting harmful steam and moisture into the crawlspace (Items 2 and 3).
Permanent dryer ducts must be made of rigid, smooth-wall materials and secured with approved straps or
hangers and vented to the exterior atmosphere with a reverse airflow damper shroud (Item 4). Flexible or
semi-flexible dryer ducts are not permitted for use in permanent or non-serviceable areas. They will clog
and can overheat causing fires. They can deteriorate and introduce damaging moisture into structure. At
best they will significantly reduce dryer efficiency and performance. Recommend proper and professional
repairs be completed by a qualified duct cleaning and installation contractor.
8.3 (Item 2)
8.3 (Item 3)
8.3 (Item 4)
|
|
(3) SAFETY ADVISORY- Dryer ducts should be cleaned and inspected annually for proper performance.
Dryer ducts are susceptible to clogging and blockage due to lint and moisture build up. Restricted dryer
vents will not only reduce drying efficiency, but worse they can overheat and cause fires.
If your dryer used a vinyl or foil flex duct connector you should dispose of it and replace with flexible aluminum duct. Aluminum duct is the most efficient type, safest type to reduce fire hazards and the only type recommended by dryer manufactures and by most municipal building codes. Dryer vent installation guidelines See more about dryer duct safety here. |
GENERAL APPLIANCE CONDITION / RATING:
Good (No significant concerns, functioning as designed) |
GARBAGE DISPOSAL:
Functional |
DISHWASHER:
Functional |
RANGE/OVEN/STOVE/COOK TOP:
Functional |
MICROWAVE OVEN (built in):
Functional |
STOVE EXHAUST / RANGE HOOD:
Functional Not vented to exterior. Recirculate type. |
INDOOR DOWN DRAFT GRILL:
None installed |
TRASH COMPACTOR:
None installed |
9.0 |
DISHWASHER
Comments and observations: Inspected |
9.1 |
RANGES/OVENS/COOKTOPS
Comments and observations: Inspected |
9.2 |
RANGE HOOD
Comments and observations: Inspected |
9.3 |
GARBAGE DISPOSAL UNIT
Comments and observations: Inspected |
9.4 |
MICROWAVE COOKING EQUIPMENT
Comments and observations: Inspected |